Sun Microsystems, Inc.
spacer spacer
spacer   Sun System Handbook Home | Systems | Components | General Info | Search | Feedback 
spacer
black dot
 
black fade
 

Sun StorEdge[tm] 9910/9960 Array: Hardware Specifications

Disks (System Capacity)
Number of disk drives (with spares)

9910: 5 to 48
9960: 5 to 512

Hot spares (maximum) 9910: 4
9960: 16
Individual disk capacities, 3-in form factor, 10K RPM 18 GB, 72 GB, 181 GB
Total raw capacity per system 9910: 8.7 TB
9960: 94.9 TB
Data Cache
Maximum 9910: 16 GB
9960: 32 GB
Minimum 9910: 1 GB
9960: 2 GB
Control Memory
Up to 1.5 GB
Logical Device Support
Up to 4096
Client-Host Interface Processors (CHIP)
Number of CHIP pairs 9910: Up to 3
9960: Up to 4
Simultaneous data transfers per CHIP pair 4 or 8
Physical interfaces per CHIP pair 4 or 8
Physical Interfaces per System
Physical Interfaces per System 9910: 24
9960: 32
Fibre Channel (fiber-optic cable) 9910: 0, 4, 8, 12, 16, 20, or 24
9960: 0, 4, 8, 12, 16, 20, 24, 28, or 32
Extended Serial Adapters 9910: 0, 4, 8, 12, 16, 20, or 24
9960: 0, 4, 8, 12, 16, 20, 24, 28, or 32
Array Control Processor
Number of ACP pairs per system 9910: 1
9960: Up to 4
Physical array paths per ACP pair 8
Maximum disks per array path 9910: 12
9960: 32
Simultaneous transfers per ACP pair
To cache
9910: 4
9960: 8
To disk array
8
Transfer rates  
Per disk array path
Up to 100 MB/sec
Per ACP pair (to cache)
Up to 800 MB/sec
Per fully configured system
9910: 3.2 GB/sec
9960: 6.4 GB/sec
Environment
Power 9910: 3.3 kVA
9960 (Control Frame): 1.6 kVA
9960 (Array Frame):
3.7 kVA (1-4); 2.9 kVA (5-6)
Heat 9910: 3.1 kW
9960 (Control Frame): 1.5 kW
9960 (Array Frame): 3.4 kW (1-4); 2.6 kW (5-6)
Temperature & Humidity

Operating1: 60 (16) to 90 (32), 20% to 80% relative humidity.

Non-Operating: 14 (-10) to 109 (43), 8% - 90 % relative humidity.

1 Environmental specification for operating condition should be satisfied before the disk subsystem is powered on. The maximum temperature of 90F (32C) should be strictly satisfied at the air inlet portion of the subsystem. The recommended temperature range is 70-75F (21-24C).
Dimensions and Weights
Height 1,790 mm (70.5 in.)
Width (with two side panels) 9910: 700 mm (27.6 in.)
9960 (Control Frame): 750 mm (29.5 in.)
9960 (Array Frame): 600 mm (23.6 in.)
Depth 800 mm (31.5 in.)
Weight 9910: 524 kg (1,153 lb.)
9960 (Control Frame): 451 kg (992 lb.)
9960 (Array Frame): 469 kg (1,031 lb.)

Power Connectors
System Geography Power Quantity Plug Connector
9910 US Single-Phase
2
Russellstoll 3720DP
N/A - Controller
Russellstoll 3913 or Russellstoll 3743
N/A - Controller
Europe Single-Phase
2
N/A (Hardwire)
N/A - Controller
N/A (Hardwire)
N/A - Controller
9960 (Control Frame) US Single-Phase
2
Russellstoll 3720DP Russellstoll 3913 or Russellstoll 3743
3-Phase
0
N/A Powered from first Array Frame N/A Powered from first Array Frame
Europe Single-Phase
2
N/A (Hardwire) N/A (Hardwire)
3-Phase
0
N/A Powered from first Array Frame N/A Powered from first Array Frame
9960 (Array Frame) US Single-Phase
2
Russellstoll 3720DP Russellstoll 3913 or Russellstoll 3743
3-Phase
2
Russellstoll 3760 or Russellstoll 3760PDG Russellstoll 3754 or Russellstoll 3934
Europe Single-Phase
2
N/A (Hardwire) N/A (Hardwire)
3-Phase
2
N/A (Hardwire) N/A (Hardwire)

 


WebToneWebToneWebToneWebTone
 Copyright 1994-2003 Sun Microsystems, Inc.,  901 San Antonio Road, Palo Alto, CA 94303 USA.  All rights reserved.
 Legal Terms Privacy Policy Feedback