Power Data for A3500 Configurations: 1. 7200 RPM Disk Drives: ~~~~~~~~~~~~~~~~~~~~~ AC RMS current* Configs BTU Watt VA @200VAC @240VAC ------------ ----- ---- ---- ------- ------- 1x5x9GB Min 2416 708 787 3.94 3.28 1x5x18GB Min 2611 765 850 4.25 3.54 1x5x9GB Max 6317 1851 2057 10.29 8.57 1x5x18GB Max 5539 1623 1803 9.02 7.51 2x7x9GB Min 4160 1219 1354 6.77 5.64 2x7x18GB Min 4549 1333 1481 7.41 6.17 2x7x9GB Max 9153 2682 2980 14.90 12.42 2x7x18GB Max 8058 2361 2623 13.12 10.93 3x15x9GB Max 18956 5554 6171 N/A N/A 1x8x9GB rack** 9803 2872 3191 15.96 13.30 3x15x18GB Max 16614 4868 5409 N/A N/A 1x8x18GB rack** 8556 2507 2786 13.93 11.61 2. 10Krpm Disk Drives: ~~~~~~~~~~~~~~~~~~~ AC RMS current* Configs BTU Watt VA @200VAC @240VAC ------------ ----- ---- ---- ------- ------- 1x2x9GB Min 1517 445 494 2.47 2.06 1x2x9GB Max 2628 770 856 4.28 3.56 1x5x9GB Min 2331 683 759 3.80 3.16 1x5x9GB Max 5802 1700 1889 9.45 7.87 2x7x9GB Min 3293 965 1072 5.36 4.47 2x7x9GB Max 8431 2470 2745 13.73 11.44 3x15x9GB Max 17407 5100 5667 N/A N/A 1x8x9GB rack** 8977 2630 2922 14.61 12.18 For upgrade with additional drives add the following figures per drive: AC RMS current* BTU Watt VA @200VAC @240VAC ----- ---- ---- ------- ------- 9GB/7200rpm: 77.8 22.8 25.33 0.127 0.106 18GB/7200rpm: 97.6 28.6 31.80 0.159 0.132 9GB/10Krpm: 69.4 20.3 22.60 0.113 0.094 * The AC RMS current is the calculated rack AC input current assuming only one power sequencer is operational. Calculation is based on 0.9 power factor, 70% power supply efficiency on the A3000 and D1000 power supplies. ** The 3x15 configuration consists of two racks: a 2x7 rack and a 1x8 rack. For the 2x7 rack power data refer to the 2x7 max configuration. 3. StorEdge A3000 and StorEdge A3500 cold start initial surge current specification: Tray level initial surge current specification: ----------------------------------------------- RSM disk tray, each power supply: 15 A rms or 21 A peak for one line cycle. StorEdge A3000 controller module, each power supply: 25 A rms or 35 A peak for one line cycle. StorEdge D1000 disk tray, each power supply: 11 A rms or 22 A peak for one line cycle. Rack level initial surge current specification: ----------------------------------------------- StorEdge A3000 (StorEdge A3000 controller with RSM disk tray in 56" rack) 1x5 configuration, per power cord: 120 A rms for one line cycle or 169 A peak. StorEdge A3500 (StorEdge A3000 controller with D1000 disk tray in 72" rack) 1x2 configuration*, per power cord: 47 A rms for one line cycle or 79 A peak. 1x5 configuration, per power cord: 44 A rms for one line cycle or 88 A peak. 2x7 configuration, per power cord: 72 A rms for one line cycle or 114 A peak. 1x8 configuration, per power cord: 55 A rms for one line cycle or 110 A peak. * Assume the rack contains only one 1x2 configuration. The A3000 controller and the two D1000 trays are powered off from one sequenced output.