FCO #: A0172-1

SYNOPSIS: Delorean racks shipped before July 12, 1999 may have unusable
          Anti-Tip rails

DATE: Feb/27/2001

KEYWORDS: Delorean racks shipped before July 12, 1999 may have unusable
          Anti-Tip rails


---------------------------------------------------------------------
- Sun Proprietary/Confidential: Internal Use Only -
---------------------------------------------------------------------  
                               FIELD CHANGE ORDER
                  (For Authorized Distribution by SunService)


SYNOPSIS:  Delorean racks shipped before July 12, 1999 may have
           unusable Anti-Tip rails.
                     
TOP FIN/FCO REPORT: No
PRODUCT_REFERENCE:  Delorean 72-inch StorEdge Cabinet

PRODUCT CATEGORY:  Storage / Service

PRODUCT AFFECTED:

Mkt_ID        Platform   Model  Description              Serial Number
------	      --------   -----  -----------              -------------

Systems Affected:
------- --------
  -            ANYSYS      -    System Platform Independent     -
  
X-Options Affected
--------- -------
SG-XARY350A-545G   -       -    A3500 1x5x9GB/7200 max          -
SG-XARY351A-180G   -       -    A3500 1x5x18GB/7200 min         -
SG-XARY352A-180G   -       -    A3500 2x7x9GB/7200 min          -
SG-XARY352A-763G   -       -    A3500 2x7x9GB/7200 max          -
SG-XARY353A-360G   -       -    A3500 2x7x18GB/7200 min         -
SG-XARY354A-1635G  -       -    A3500 3x15x9GB/7200 max         -
SG-XARY360A-90G    -       -    A3500 1x5x9GB/10K min -BSD      -
SG-XARY350A-90G    -       -    A3500 1x5x9GB/7200 min          -
SG-XARY360A-545G   -       -    A3500 1x5x9GB/10K max           -
SG-XARY362A-180G   -       -    A3500 2x7x9GB/10K min -BSD      -
SG-XARY364A-1635G  -       -    A3500 3x15x9GB/10K max          -
SG-XARY374A-273G   -       -    A3500 3x15x9GB/10K min - BSD    -
SG-XARY380A-1092G  -       -    A3500 1x5x18GB/10K max          -
SG-XARY382A-364G   -       -    A3500 2x7x18GB/10K min - BSD    -
SG-XARY384A-546G   -       -    A3500 3x15x18GB/10 min - BSD    -
SG-XARY381A-364G   -       -    A3500 1x5x36GB/10K min - BSD    -
SG-XARY381A-1456G  -       -    A3500 1x5x36GB/10K max          -
SG-XARY383A-728G   -       -    A3500 2x7x36GB/10K min - BSD    -
SG-XARY385A-1092G  -       -    A3500 3x15x36/10K min - BSD     -

SG-XARY553A-509G   -       -    1 X 509.6GB A5100 Array in a    -
                                72-inch Cabinet

SG-XARY553A-1019G  -       -    2 X 509.6GB A5100 Array in a    -
                                72-inch Cabinet

SG-XARY553A-3057G  -       -    6 X 509.6GB A5100 Array in a    -
                                72-inch Cabinet

SG-XARY523A-200G   -       -    1 X 200.2GB A5200 Array in a    -
                                72-inch Cabinet

SG-XARY523A-400G   -       -    2 X 200.2GB A5200 Array in a    -
                                72-inch Cabinet

SG-XARY523A-1200G  -       -    6 X 200.2GB A5200 Array in a    -
                                72-inch Cabinet

SG-XARY543A-400G   -       -    1 X 400.4GB A5200 Array in a    -
                                72-inch Cabinet

SG-XARY543A-800G   -       -    2 X 400.4GB A5200 Array in a    -
                                72-inch Cabinet

SG-XARY543A-2400G  -       -    6 X 400.4GB A5200 Array in a    -
                                72-inch Cabinet
SG-XARY380A-182G   -       -    A3500 1x5x18GB/10K min -BSD     -

AFFECTED PARTS:

Part Number       	Description         	Model
-----------		-----------		-----
N/A

(SCSI Devices)
Type    Vendor    Model     SerialNumber(Min)    SerialNumber(Max)    Firmware
----    ------    -------   ------------------   ------------------   --------
N/A


REFERENCES :
   ECO: WO_18885     
   BugID: 4292662      
   ESC: 523538       
   ECO: WO_19451     
   LEAP: 1318         
   LEAP: 1401
   MANUAL: 805-3067-12  Sun StorEdge Exp Cabinet Installation and Service
Manual

PROBLEM DESCRIPTION :

Delorean 72-inch StorEdge Cabinets shipped before July 12, 1999 may have
unusable Anti-Tilt stabilizer rails.

During installation of a 72-inch StorEdge Cabinet it may become apparent that
it is not possible to fit the Anti-Tilt stabilizer rails to the cabinet screw
studs.  Some rails may fit initially, but subsequently they may bind in use or
become completely jammed.  This may make the rails unusable.  In some cases
rails may even fall off, as persistent binding can loosen the screw-in studs.
This problem may become apparent some time after installation, following a
number of rail extension and retraction operations.

In the event that equipment in the 72" StorEdge cabinet is serviced without
the
rails being properly extended the rack may become unstable.

The root cause was determined to be related to the stabilizer's channel depth
which needed to be deeper.  New Anti-tilt stabilizer rails were created to
correct this issue.

All 72-inch StorEdge Cabinets shipped since July 12, 1999 have this new style
Anti-tilt stabilizer.  Corrective action was made available in Enterprise
Services via the release of a Rack Stabilizer Kit (Sun p/n 370-4342-01) via
ECO# WO_19451 as of January 19, 2001 and LEAPs 1318 and 1401.

IMPLEMENTATION :

 ---
|   |   MANDATORY (Fully Pro-Active)
 ---

 ---
| X |   CONTROLLED PRO-ACTIVE (per Sun Geo Plan)
 ---

 ---
|   |   REACTIVE (As Required)
 ---

REPLACEMENT TIME ESTIMATE : 0.5 hours

SPECIAL CONSIDERATION :


CORRECTIVE ACTION :

Upon failure (or need) or at customer request install Rack Stabilizer Kit
(Sun p/n 370-4342-01) per instructions included with kit.

Reference the Sun StorEdge Expansion Cabinet Installation and Service Manual
(Sun p/n 805-3067-11, page 1-5 and 1-6) for installation information.

COMMENTS :

BILLING TYPE:

 Warranty: Sun will provide parts at no charge under Warranty
           Service. On-Site Labor Rates are based on how the
           system was initially installed.

 Contract: Sun will provide parts at no charge. On-Site Labor Rates
           are based on the type of service contract.

 Non Contract: Sun will provide parts at no charge. Installation by
               Sun is available based on the On-Site Labor Rates
               defined in the Price List.

--------------------------------------------------------------------------
Implementation Footnote:
________________________

i)   In case of Mandatory FCOs, Enterprise Services will attempt to contact
      all known customers to recommend the part upgrade.

ii)  For controlled proactive swap FCOs, Enterprise Services mission critical
     support teams will initiate proactive swap efforts for their respective
     accounts, as required.

iii) For Replace upon Failure FCOs, Enterprise Services partners will implement

     the necessary corrective actions as and when they are required.

--------------------------------------------------------------------------

All released FINs and FCOs can be accessed using your favorite network
browser as follows:

SunWeb Access:
______________

* Access the top level URL of http://sdpsweb.EBay/FIN_FCO/

* From there, select the appropriate link to query or browse the FIN and
  FCO Homepage collections.

SunSolve Online Access:
_______________________

* Access the SunSolve Online URL at http://sunsolve.Central/

* From there, select the appropriate link to browse the FIN or FCO index.

Supporting Documents:
____________________

Supporting documents for FIN/FCOs can be found on Edist.  Edist can be
accessed internally at the following URL: http://edist.Central/.

* From there, follow the hyperlink path of "Sun Service Documentation"
and
  click on "FIN & FCO attachments", then choose the appropriate
folder,
  FIN or FCO.  This will display supporting directories/files for FINs or
  FCOs.

Internet Access:
_______________

* Access the top level URL of https://infoserver.Sun.COM

--------------------------------------------------------------------------
General:
________

Send questions or comments to finfco-manager@sdpsweb.EBay

---------------------------------------------------------------------------



Copyright (c) 1997-2003 Sun Microsystems, Inc.