Document fins/I0785-1


FIN #: I0785-1

SYNOPSIS: The osdTimeDeltas file is used when providing the Time Of Day to Sun
          Fire 15K domains.  This file was not included in the list of files to
          propagate from the MAIN SC to the SPARE SC

DATE: Mar/01/02

KEYWORDS: The osdTimeDeltas file is used when providing the Time Of Day to Sun
          Fire 15K domains.  This file was not included in the list of files to
          propagate from the MAIN SC to the SPARE SC


---------------------------------------------------------------------
- Sun Proprietary/Confidential: Internal Use Only -
---------------------------------------------------------------------  
                            FIELD INFORMATION NOTICE
                  (For Authorized Distribution by SunService)



SYNOPSIS: The osdTimeDeltas file is used when providing the Time Of Day
	  to Sun Fire 15K domains.  This file was not included in the list
          of files to propagate from the MAIN SC to the SPARE SC.


SunAlert:           No

TOP FIN/FCO REPORT: No 
 
PRODUCT_REFERENCE:  osdTimeDeltas file on F15K  
 
PRODUCT CATEGORY:   Server / Service 


PRODUCTS AFFECTED:

Systems Affected
----------------    
Mkt_ID   Platform   Model   Description       Serial Number
------   --------   -----   -----------       -------------
  -        F15K      ALL    Sun Fire 15000          -


X-Options Affected
------------------

Mkt_ID   Platform   Model   Description       Serial Number
------   --------   -----   -----------       -------------
  -         -         -          -                  -

PART NUMBERS AFFECTED:

Part Number   Description                       Model
-----------   --------------------              -----
501-5121-10   System Control Bd Sun Fire 15K      -


REFERENCES:

BugId: 4628978 - osdTimeDeltas missing from fomd_sys_datasync.cf.

      
PROBLEM DESCRIPTION:

The osdTimeDeltas file is used when providing the Time Of Day to Sun
Fire 15K domains.  This file was not included in the list of files to
propagate from the MAIN SC to the SPARE SC.

All Sun Fire 15K systems running SMS 1.1 or SMS 1.2 do not have the
osdTimeDeltas file in the file propagation list.  If a failover occurs,
this could result in a rollback of a domain's Time Of Day.  Such a shift
in time has unforseen effects on applications.

The osdTimeDeltas holds the time offsets for the domains.  This is
essential to deliver the proper VTOD to the domain and OBP download
time.  But, current entries in the fomd_sys_datasync.cf file do not
cover propagation of this file.

If not propagated, incorrect VTOD could be delivered to a domain. 
If this rolls the clock backwards, it can have terrible consequences
on an applications. 

This issue was caused by an oversight during SMS development.  The
osdTimeDeltas file was not included in the list of system files to be
propagated.

System Controllers must be manually adjusted to include the
osdTimeDeltas files in the propagation list. 

A software patch for SMS 1.2 is planned. Currently, there is no patch
ID defined or released.  SMS 1.1 will not be patched.


IMPLEMENTATION: 
 
         ---
        |   |   MANDATORY (Fully Pro-Active)
         ---    
         
  
         ---
        |   |   CONTROLLED PRO-ACTIVE (per Sun Geo Plan) 
         --- 
         
                                
         ---
        | X |   REACTIVE (As Required)
         ---
         

CORRECTIVE ACTION:

An Authorized Enterprise Services Field Service Representative may avoid 
the above mentioned problems by following the recommendations as shown
below.   

Please perform the following workaround for SMS 1.1 and 1.2 until 
a patch becomes available.

A software patch for SMS 1.2 is planned. Currently, there is no patch
ID defined or released.  SMS 1.1 will not be patched.

On the MAIN System Controller, perform the following steps as root:

   1. Change directory to /etc/opt/SUNWSMS/config

      # cd /etc/opt/SUNWSMS/config

   2. Add the following line to the fomd_sys_datasync.cf file:

      /var/opt/SUNWSMS/data/osdTimeDeltas:1:1

   3. Stop and restart SMS.

      # /etc/init.d/sms stop
      # /etc/init.d/sms start

4. Repeat Steps 1-3 on the SPARE System Controller.


COMMENTS: 

None.

-------------------------------------------------------------------------

Implementation Footnote:

i)   In case of MANDATORY FINs, Enterprise Services will attempt to    
     contact all affected customers to recommend implementation of 
     the FIN. 
   
ii)  For CONTROLLED PROACTIVE FINs, Enterprise Services mission critical    
     support teams will recommend implementation of the FIN  (to their  
     respective accounts), at the convenience of the customer. 

iii) For REACTIVE FINs, Enterprise Services will implement the FIN as the   
     need arises.
----------------------------------------------------------------------------
All released FINs and FCOs can be accessed using your favorite network 
browser as follows:
 
SunWeb Access:
-------------- 
* Access the top level URL of http://sdpsweb.ebay/FIN_FCO/

* From there, select the appropriate link to query or browse the FIN and
  FCO Homepage collections.
 
SunSolve Online Access:
-----------------------
* Access the SunSolve Online URL at http://sunsolve.Corp/

* From there, select the appropriate link to browse the FIN or FCO index.

Internet Access:
----------------
* Access the top level URL of https://infoserver.Sun.COM
--------------------------------------------------------------------------
General:
--------
* Send questions or comments to finfco-manager@sdpsweb.EBay
--------------------------------------------------------------------------


Copyright (c) 1997-2003 Sun Microsystems, Inc.