Disks
36.4 GB Seagate ST136403FC (36.4GB 10000 RPM FC-AL)
Seagate ST336704FC (36.4GB 10000 RPM FC-AL)
IBM DDYF-T36950 (36.4GB 10000 RPM FC-AL)
Seagate ST336605FC (36.4GB 10000 RPM FC-AL)
Seagate ST336752FC (36.4GB 15000 RPM FC-AL)
73.4 GB Seagate ST173404FC (73.4GB 10000 RPM FC-AL)
Seagate ST373405FC (73.4GB 10000 RPM FC-AL)
181 GB Seagate ST1181677FCV (181.5GB 7200 RPM FC-AL)
Capacity
3900: 655 GB to 29 TB
6900: 655 GB to 26 TB
Processor
500MHz, 64-bit UltraSPARC IIe
Memory
Minimum 512MB, expandable to 1GB
Environment
AC Power 200 - 240 VAC @ 47 to 53 Hz Single phase
Heat Output 3910: ~14000 BTU
3960: ~26000 BTU1
6910: ~14000 BTU
6960: ~26000 BTU1
Temperature Operating: 5º C to 35º C (41º F to 95º F)
Nonoperating: -20º C to 60º C (-4º F to 140º F)
Humidity Operating: 20% to 80% relative humidity, noncondensing s7º C (80.6º F) maximum wet bulb
Nonoperating: 5% to 93% relative humidity, noncondensing
Altitude Operating: -305 to 3048 meters (-1000 to 10000 feet)
Nonoperating: -305 to 12192 meters (-1000 to 40000 feet)
Shock Operating: 4.0g for maximum duration of 11ms (half-sinewave)
Nonoperating: 10.0g for maximum duration of 11ms (half-sinewave)
Vibration Operating: 5 to 500 Hz @ 0.25g sinusoidal
Nonoperating: 5 to 500 Hz @ 1.0g sinusoidal
Plug Type - U.S. NEMA L6-30P for 200 to 240 VAC
Plug Type - International 32A, single phase IEX 309, connected for 220 to 240 VAC
1 - 3960 and 6960 values include the Sun StorEdge Expansion Cabinet.
Dimensions and Weights
Height 190.5 cm (75 in.)
Width 3910: 60.7 cm (23.9 in.)
3960: 122 cm (47.8 in.)
6910: 60.7 cm (23.9 in.)
6960: 122 cm (47.8 in.)
Depth 94 cm (37 in.)
Weight1 3910: 665 kg (1466 lbs.)
3960: 1295 kg (2855 lbs.)2
6910: 549 kg (1210 lbs.)
6960: 1314 kg (2896 lbs.)2
Power Cord 4.6 m (15 ft.)
1 - Values given are for the maximum hardware configuration available.
2 - 3960 and 6960 values include the Sun StorEdge Expansion Cabinet.
Regulations
Meets or exceeds the following requirements:
Safety IEC 60950, EN 60950, UL 60950, UL 1950, FCC Part 15 (47CRF15B), CISPR 22 (EN55022 - RF Radiated and Conducted Emissions), IEC 61000-3-2, IEC 61000-3-3
Immunity CISPR 24 (EN55024), IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
Clearance and Service Access
Front With Service Access: 122 cm (48 in.)
Without Service Access: 61cm (24 in.)
Rear With Service Access: 92 cm (36 in.)
Without Service Access: 61 cm (24 in.)
Left1 With Service Access: 92 cm (36 in.)
Without Service Access: 5 cm (2 in.)2
Right1 With Service Access: 92 cm (36 in.)
Without Service Access: 0